2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 1/8 Abstract— In Voltage Sourced Converter (VSC) based HVDC systems, the existing harmonics on one side ac system will be transferred through the dc-link to the other side ac system and induce a series of harmonics that tend to be more than the origin. This is also true for the case of one side unsymmetrical ac system; the fundamental negative-sequence component will be transferred to the dc-link with the second harmonic is dominant, which in turn causing a series of harmonics on the other side ac system. This paper describes the operation of VSC using three switching functions, which include a fundamental component and carrier sideband components, using double-edge naturally sampled PWM to yield their harmonic spectra. The space vector representation of the VSC’s switching functions is used as a tool for analyzing and giving the detailed rules of VSC’s harmonic interaction, and from that, analyzing harmonic propagation through the dc-link. Based on the methodological analysis, the simulation model of a suggested project for Northwest power grid - China is built and implemented using MATLAB/SIMULINK. In the investigation of harmonic propagation, simulation results show that, the amplitude of transferred harmonics through the dc-link may be amplified due to the resonance causing harmonic instability. This deep understanding of VSC-based HVDC system’s harmonic propagation characteristic could be beneficial to harmonic mitigation control. Index Terms—Voltage sourced converter, VSC-based HVDC, HVDC harmonic, harmonic propagation, switching function. I. INTRODUCTION HE INTRODUCTION of Voltage-Sourced Converter (VSC)-based HVDC to power system offers the potential to improve control of power flow and enhance system stability. However, VSC-based HVDC producing harmonics on both ac-side and dc-side is inherent by the VSC itself and will interact with harmonic distortions already existed in the system. The harmonics of VSC are directly associated with the type of VSC technologies, modulation techniques and the switching frequency [1]. A more elaborate understanding of these harmonics must develop to find adequate approaches to harmonic elimination, preventing the system from instability and sizing the components of the system. Manuscript received July ..., 2014. This work was supported by State Grid Cooperation of China, Major Projects on Planning and Operation Control of Large Scale Grid SGCC-MPLG019-2012 Phuchuy Nguyen is with the School of Electrical Engineering, North China Electric Power University, Beijing 102206, P.R China (e-mail:
[email protected]). Minxiao Han is with the School of Electrical Engineering, North China Electric Power University, Beijing 102206, P.R China (e-mail:
[email protected]). Harmonic interactions between the two sides of the converter and through the dc-link of HVDC are analyzed in [2] where the converter is a current-source converter (CSC). In the case of VSC, a practical case in [3] shows that harmonic instability may occur if there is an unbalanced second harmonic generated by a nearby saturated transformer on the ac-side of VSC. Based on analyzing basic current and voltage equations of CSC and VSC, the authors in [4] establish simple rules of harmonic transfer through converters by using switching functions represented in space vector form. This additional understanding of harmonic interaction is quite adequate to the analytical and simulation results in [2] and [3]. The dc equivalent impedance of VSC is formulated by analyzing the harmonic transfer across converter in [5]. It is convenient for harmonic resonance analysis. This paper presents harmonic transfer rules of VSC. They are suitable for both two-level and three-level converters, not only valid for voltage harmonics, but also for current harmonics. The rules were built after analyzing VSC in both balanced and unbalanced operating conditions by using switching functions represented in space vector forms. Unlike previous works just used the fundamental switching component, this paper also presents the rules of harmonic transfer under the interaction of higher order switching components. These rules are adopted for both positive- and negative-sequence harmonics, accounting for all harmonics propagated through the dc-link of VSC-based HVDC. Based on these rules, the dc- and ac-equivalent impedances of VSC were calculated to give a clearer view of the harmonic propagation. The paper has five sections. The first section describes VSC-based HVDC system suggested for Northwest power grid – China, used to study harmonic interaction and harmonic propagation. The second section represents the principle operation of VSC describing the relationships between both side quantities under space vector representation. Also, the switching function of both two-level and three-level converters are calculated depending on the adopted PWM techniques, applying double Fourier integral analysis. Thereafter, the rules of harmonic transfer through VSC are established and applied to VSC-based HVDC harmonic propagation. The equivalent impedances are also used to analyze this propagation. Finally, a Matlab/Simulink model of the VSC-based HVDC system is built to validate the method. II. VSC-BASED HVDC SYSTEM Study on Harmonic Propagation of VSC-based HVDC Systems Phuchuy Nguyen, Minxiao Han, North China Electric Power University, Beijing 102206, China T 2146 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 2/8 Cable Cable AC system 1 330 kV AC system 2 230 kV Trans. Reactor AC filter Reactor AC filter Trans. Cd Cd Cd Cd Fi lte r Fi lte r Fi lte r Fi lte r Fig. 1. Schematic of study VSC-based HVDC. tua tub tuc tka tkb tkc tia tib tic pu t dC2 dC2 1 -1 -1 -1 1 1 nu t 0 0 0 di t Fig. 2. Three-level voltage sourced converter phase quantities. apk t ank t 0 1 1 2 Fig. 3. Step functions of phase a The VSC-based HVDC system is a point-to-point scheme which consists of two VSC stations interconnected by 300 kV dc cables and transfers power from 330 kV ac system to 230 kV ac system. Figure 1 represents the system configuration and its main components. To smooth ac-side output current of the VSC, a three-phase smoothing converter reactor is placed between the converter and a converter transformer. The transformer winding is Yn/Y connection type where the Y winding is connected to the reactor, resulting in decoupling the ac system from the triple harmonics produced by the converter. The ac high-pass filter group is an essential part of the scheme, located between the converter transformer and the converter reactor for improving filtering characteristic. On the dc-side of VSC, the reservoir dc capacitors are used to equalize dc voltage, enhance the system dynamics, and reduce the dc-side voltage ripple. The third order tuned filters are connected in parallel with dc capacitors to suppress the dominant third order voltage ripple caused by the capacitors. Moreover, dc-smoothing reactors are also used to smooth dc-side current. III. VOLTAGE SOURCED CONVERTERS A. Operation principle Voltage source converters (VSC) convert a stiff dc voltage source to ac voltage outputs. For a three-phase VSC connected to three-phase ac system, communication takes place between valves connected to the same phase. By switching the correct IGBTs sequentially at the correct times, the VSC’s three output-sets can be created at the desired frequency. The various valve-switching techniques are applied to give different numbers of harmonic contents and ac voltage magnitude. In Figure 2, a three-level Neutral Point Clamped (NPC) VSC forces the ac-side voltage to a certain value determined by the given switching functions. The switching functions take the value 1xk , whenever phase ‘x’ is switched to the negative dc pole, and the value 1xk when it is switched to the positive dc pole, otherwise, 0xk when it is switched to the “midpoint.” For the VSC using pulse-width modulation technique, the 1xk corresponds to the positive half cycle modulation wave, in contrast, the 1xk corresponds to the negative half cycle modulation wave. In general, the relationships between the ac- and dc-side quantities of VSC can be determined by (1). a a ad b b bd c c cd u t k t u t u t k t u t u t k t u t )1( where xk t : switching function of phase x (x=a, b, c). xd p xp n xnu t u t k t u t k t (2) In (2), pu t and nu t are dc-side positive and negative pole voltages, respectively; xpk t and xnk t are step functions corresponding to each half cycle of phase x modulation wave, as shown in Fig.3. It can be seen that, for phase a, ( ) ( ) 1ap ank t k t and ( ) ( )ap ank t k t is a periodic function, and thus can be expanded by a Fourier series as [6] 0 1,3,5... 4 1 sin cos 2ap an h h thtktk h . (3) Adding -2 /3 and 2 /3 to the phase angle of each harmonic component in (3) will derive the corresponding forms of phase b and c, respectively. The dc-side current on the positive dc pole is established in (4). / 2.d a a b b c ci t k t i t k t i t k t i t (4) If the dc-side voltage / 2p n du t u t u t , the relationships between the ac- and dc-side quantities of VSC, without the zero-sequence components, now can be determined in the form of the space vector [4]: / 2dVu t K t u t )5( *3 Re 4 Vd i t K t i t (6) 2147 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 3/8 where ,V Vu t i t : space vector of ac-side voltage and current. ,d du t i t : dc-side voltage and current. K t : the space vector of three sinusoidal switching functions. 22 3 a b c K t k t a k t a k t (7) 2 /3ja e B. Harmonics in two-level converters The PWM double-edge natural sampling process involving the comparison of a modulating sinusoidal wave with a high frequency triangular carrier, and the single-phase modulation technique is adopted to minimize harmonic distortion. In addition, the double Fourier integral analysis can be used as the most well-known analytical method to determine the harmonic spectrum of the converter’s output. The analytical expression of switching function of phase x in the time domain is given by the following equation [7]: 0 1 0 cos / 2 sin / 22 cos xx n m n xc k t M t J mM m n m m t n t (8) where x : a,b, c M : Modulation index. 0 : Frequency of the modulation wave. c : Frequency of the carrier wave. m : Group index (multiple of switching frequency). n : Sideband harmonic index from each group. x : Modulation wave phase shift for each phase a, b, or c. : Carrier wave phase shift. nJ : First kind Bessel function (see Appendix). The first term in (8) gives the fundamental component, and the second term gives the harmonic groups of each multiple of the carrier frequency and its sidebands. Because sin / 2 0m n with any m+n are even numbers; therefore, there are no harmonics at the even multiples of the carrier frequency. The sideband harmonics are of m c+n 0, with the limits of m+n are odd numbers. C. Harmonics in three-level converters The naturally sampled phase disposition PWM is adopted to compare modulating sinusoidal waves with two high frequency triangular carriers. Using the same analytical method as two-level converter, the analytical expression of switching function of phase x of a three-level converter in the time domain is given by the following equation [8]: 0 2 1 2,4,6... 0 2 1,3,5... 0 cos cos2 1 cos 2 1 cos8 1 cos 2 xx n m n xc k mn m n xc k t M t J m M n m m t n t J n m m t n t (9) where 2 1 1 2 1 2 1 2 2 1 2 2 1 k mn k k k J J m M k n k n (10) 2 1 2 1,n kJ J : First kind Bessel function (see Appendix A). Similar to two-level converters, the first term in (9) gives the fundamental component of switching function. Its amplitude just is dependent on the modulation index but is independent of the frequency index, mf = c/ 0, and carrier phase shift. The amplitudes of other harmonics depend on the characteristic of the Bessel function, which are equal for two sideband harmonics on opposite sides of the center-placed harmonic in each group. It is obvious that, the even- and odd-sideband harmonics only exist around the odd- and even-carrier multiples respectively. As a result, the characteristic harmonics on the ac-side of VSC have odd orders. IV. VSC’S HARMONIC INTERACTION RULES A. Space vector representations As can be seen from (8) and (9), each switching function includes fundamental switching component and high-order switching components. The high-order components satisfy m.mf+n=N(0)=3i, where i is an integer of the fundamental, are called zero-sequence switching components. It is clear from (4) that the dc-side current is not affected by the zero-sequence switching components. For the high-order switching components satisfy m.mf+n=N(+)=3i+1 are called positive-sequence switching components. Also, the other high-order components satisfy m.mf+n=N(-)=3i-1 are called negative-sequence switching components. Consequently, the space vector of switching functions is composed of three components expressed as the following equation: 1 11 nmnm m n m n K t K t K t K t (11) where 0 0 0 1 3 1 3 1 ˆ ˆ j t j i t mn mn j i t mn mn K t Me K t K e K t K e )21( ˆ mnK and ˆ mnK are different for which either a two-level converter or a three-level converter is used, but the same switching component will have the same interaction. It can be seen from (11), the zero-sequence switching components, which has triple orders, does not appear. 2148 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 4/8 B. DC capacitor voltage ripples transfer to AC-side In the light of dc capacitors working as voltage dividers, the voltages on dc capacitors are composed of a third harmonic and higher-order harmonics around switching frequency. The dominant third harmonic component can be expressed as (13). Its amplitude decreases with the increase in not only power factor of the converter, but also the chosen dc capacitors [6]. 3 3 0cos 3r ru t U t (13) The dc-side positive and negative pole voltage now can be written as the following equation 3 0 3 0 / 2 cos 3 / 2 cos 3 p d r n d r u t U U t u t U U t (14) As above expression in (3) which includes zero-sequence harmonics, the space vector representation in (5) is not suitable for harmonic transfer analyzing in this case. From (1), (2), (3) and (14), and just considering the fundamental switching component in (9), the phase a output voltage is: 01 3 0 1,3,5... 3 0 1,3,5... cos 2 1 sin cos 4 2 1 sin cos 2 2 dc a r h r h MUu t t MU h h t h MU h h t h (15) From (15), the additional harmonics in the ac-side will shift 2 or 4 orders from the switching component, say, the fundamental in this case. The dominant ac-side voltage harmonic is the 3rd harmonic followed by the smaller harmonics such as the 5th, 7th ones, etc. The magnitudes of higher order voltage harmonics are insignificant. Similarly, under the interaction of high-order switching components of a carrier multiple and its sidebands, the new harmonics will have the same sequences and orders to the characteristic harmonics. C. Harmonics from DC-side transferred to AC-side Assuming that the dc-side voltage comprises an rth harmonic written in the form as: 0 0 0ˆ ˆ 2/soc jr t jr t rdrdrdu t u r t u e e (16) As above state, under the interaction of the zero-sequence switching components, the dc-side voltage harmonic transfer through VSC can be explained in (17), the phase a output voltage for example: 00 0 0. 0 00 ˆ cosˆ cos 3 2 ˆ ˆ cos 3 cos 3 4 dr a mnr mn mn dr u r t u t K i t K u i r t i r t (17) These additional harmonics are all zero-sequence harmonics, therefore, they will not appear in phase-phase voltage. For the other switching components, substitute (16) to (2) with the expression of switching function as (12): 1 11 rnmrnmrrV m n m n u t u t u t u t (18) where 00 00 00 1 1 1 3 1 3 1 3 1 3 1 ˆ / 4 ˆ ˆ / 4 ˆ ˆ / 4 j r t j r t r dr j i r t j i r t mnr mn dr j i r t j i r t mnr mn dr u t M u e e u t K u e e u t K u e e (19) Clearly, the rth harmonic from the dc-side will transfer to the ac-side and produces two new sideband harmonics with the same amplitude. Under interaction of the fundamental switching component, the harmonic with higher order is a positive-sequence harmonic, and with lower order is a negative-sequence harmonic. Under interaction of the high-order switching components, if the order of dc-side harmonic is smaller than the order of the switching components, the sequence of the two-sideband harmonics on the ac-side is the same as the sequence of the switching components. D. Harmonics from AC-side transferred to DC-side Assuming ac-side currents superimpose an hth harmonic component expressed in space vector form as: 00ˆ ˆjh t jh t Vh h hi t i e i e )02( The first part in (20) is the positive-sequence harmonic, and the second one is the negative-sequence harmonic. Substituting (20) to (6) with the expression of switching function in (12), the dc-side harmonic current has the form as below: 1 11 dh d h dmnh dmnh m n m n i t i t i t i t (21) where 00 00 00 1 1 1 3 1 3 1 3 1 3 1 ˆ ˆ 4/eR3 ˆ ˆ ˆ 4/eR3 ˆ ˆ ˆ 4/eR3 j h t j h t hhhd j i h t j i h t hhnmhmd j i h t j i h t hhnmhmd i t M i e i e i t K i e i e i t K i e i e (22) In the case of a balanced harmonic, the ac-side has just only positive or negative-sequence harmonic. Equation (22) shows that, under the interaction of the positive-sequence switching components (including the fundamental component), there is only one sideband produced on the dc-side. The positive-sequence harmonic offers the lower order sideband, while the negative-sequence harmonic offers the higher order one. In contrast, under the interaction of the negative-sequence switching components, the positive-sequence harmonic provides the higher order sideband, but the negative-sequence harmonic offers the lower order one. When the ac-side has an unbalanced harmonic, it has both positive- and negative-sequence components as in (20). Therefore, there will be two sideband harmonics on the dc-side, but their amplitudes depend on the amplitude of the origin components on the ac-side, respectively. Now, an example of a three-level VSC has frequency index mf = 27 will be examined for illustrating the above analyses of harmonic transfer between both sides of the VSC. Assuming that the dc-side voltage comprises a 6th harmonic, and just consider the fundamental switching component and the 29th-order (negative-sequence) switching component of the first group of carrier multiples. As a result, the ac-side will induce only the positive-sequence 7th harmonic, and 2149 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 5/8 negative-sequence harmonics with the orders of 5th, 23nd, and 35th. Because of cross-modulation, additional harmonics will be produced on the dc-side with the 24th order as well as the 36th order due to the fundamental component. If the 29th-order switching component is relatively large, under its interaction in this case, more additional harmonics can be produced on the dc-side, which also includes the 24th and the 36th harmonics. However, the phase rotations of these 24th and 36th harmonics will be opposite to those produced under the interaction of the fundamental switching component. V. VSC-BASED HVDC HARMONIC PROPAGATION A. Harmonic propagation rule Characteristic harmonics, which are inherent by the VSC, will be produced on the ac-side, and in-turn, these characteristic harmonics will be transferred to the dc-side again. Further, the new harmonics on the dc-link are different from the original dc component, and they will be transferred to the remote ac system to produce additional harmonics. Nonetheless, these additional harmonics will have the same order with the characteristic harmonics if the two ac systems and the converters on both terminals are the same. When the ac system 1 has background harmonics, they will be conveyed to the ac system 2 with a propagation rule as shown in Fig. 4. The rule under Fig. 4 is that, for example, when the ac system 1 has a negative-sequence 5th harmonic, a series of harmonics will be produced in the ac system 2. Under the interaction of the fundamental switching component, the positive-sequence 7th harmonic and the negative-sequence 5th harmonic are dominant. B. Harmonics transfer under unsymmetrical condition When the point of common coupling on one side of the ac system is subjected to a single phase-to-ground fault, the HVDC system will operate under unbalanced grid conditions, and VSC is quite sensitive to the negative-sequence component in the ac-side voltage [9]. Based on the theory of symmetrical components, an unbalanced three-phase current comprises three balanced components of positive-, negative- and zero-sequence components. The mathematical expression of phase “x” is the following equation: 0 00 ˆ ˆcos cos sxsxsxsi t I t I t i t (23) where ˆ ˆ,s sI I : current amplitude of positive- and negative-sequence component, respectively. : phase angle of the negative-sequence component, relative to the positive-sequence component. The space vector corresponding to three-phase current without the zero-sequence component is 00ˆ ˆ j tj t s s si t i e i e (24) Equation (24) has a similar form as (20) for unbalanced harmonics. Therefore, the rule of harmonic transfer in (22) could be applied to the case of an unsymmetrical ac system. As a result, a series of non-characteristic harmonics will be induced on the dc-side of the converter where the 2nd harmonic is dominant. Again, these harmonics are conveyed to the remote ac system and produced a series of harmonics where the positive-sequence 3rd harmonic is dominant. On the other hand, for the local converter station, the dc-side induced 2nd harmonic fed back to the ac-side to produce additional positive-sequence 3rd harmonic. Because the local ac system fault is unsymmetrical, a series of additional low-order non-characteristic harmonics will be produced on the both sides. It should be taken into account if resonance occurs in the system at any frequency. C. Impedance-Frequency Characteristic of VSC-HVDC system Figure 5 illustrates the impedance calculation model of VSC-HVDC system for studying harmonic propagation. Firstly, based on the voltage harmonic transfer rule, a voltage harmonic on the dc-side transfers to the ac system 2 with two sidebands, the equivalent impedance seen from the dc-side can be calculated by (25) [10]. 2 0 2 0 2 2 2 0 2 0 16 3 ac ac DC caca Z Z Z M Z Z (25) where 2 0acZ and 2 0acZ are the positive-sequence (PoS) and negative-sequence (NeS) equivalent impedance of the ac system 2, respectively. The equivalent impedance of the dc system takes into account dc capacitors, cables, dc filters and dc smoothing reactors. The cables provide shunt capacitance at the proportional rate to the cable length that exploited to reduce the size of the dc capacitors [11]. The cables modeled as PI model and parameters are: DC link 1ACZ 2DCZ 2acZ 2acE1acZ1ac E 1dI 2dI dcZ Fig. 5. Principle calculation model of equivalent impedances h h 1K t mnK t mnK t 1h 1N h 1N h 1K t mnK t mnK t 1h 1N h 1N h r 1K t mnK t mnK t 1r 1r 2N r 2N r 2N r 2N r 1AC 1VSC 2VSC-DC link 2AC Fig. 4. Harmonic propagation in VSC-based HVDC. (+) denote positive-sequence; (-) denote negative-sequence. 2150 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 6/8 0 5 10 15 20 0 1 2 3 Harmonic order (a) Fundamental=0.7598 , THD= 4.41% M ag (% o f F un da m en ta l) 0 5 10 15 20 0 2 4 6 Harmonic order (b) Fundamental=0.7549 , THD= 8.78% M ag (% o f F un da m en ta l) Fig. 8. Spectra of phase current on receiving ac system when sending ac system has: (a) PoS 2nd background harmonic, and (b) NeS 2nd background harmonic. cosh / 2 sinh / 2 / series c s ctnuh Z Z L Y L Z (26) where /c cab cabZ Z Y is characteristic impedance; cab cabZ Y is the cable propagation constant; L is the length of the cable; cabZ and cabY are the cable impedance and admittance per-unit length, respectively. Based on the rule of the current harmonic transferred through VSC as analyzed in part IV above, the equivalent impedance seen from the ac system 1 was calculated by the following equation [10]: 2 1 2 1 3 ' 16 '31 16 " cdCA dc ac MZ Z m Z m M Z (27) where 'dcZ is the equivalent impedance of the system on the VSC1’s dc-side; ' and "are defined by the sequence of the harmonic from the ac-side. Figure 6 represents the receiving end VSC’s dc equivalent impedance response under the interaction of the fundamental switching function. It is obvious that, the equivalent impedance at the fundamental frequency has a small value, but dramatically increases at higher frequencies. Consequently, the higher harmonic orders on the VSC’s dc-side, the lesser effects on the ac-side will be. Figure 7 plots negative equivalent impedance using calculatio n in (27) in the case of changing in the length of the cable. As can be seen, the system had no resonance at the backgrou nd 2nd harmonic and in a fault condition in the sending end ac system. Obviously, the equivalent impedances at these orders had quite small values, meaning that there were insignificant effects on the receiving end ac system. The lower plot in Fig.7 is the negative equivalent impedance response, with a reduction in the dc cable length. A resonance occurred in the case of unsymmetrical single phase-to-ground fault on the sending ac system. A practical case is that, the background harmonics in North-west Power Grid includes second harmonic order. According to the analysis result in Fig.7, the effect of this 2nd harmonic’s propagation will not be an issue. D. Simulation results and analysis For studying harmonic propagation, a Matlab/Simulink simulation model was set up for the VSC-HVDC system on Fig.1. In this model, the sending end VSC was modeled to operate as power dispatcher while the receiving end VSC was modeled to operate as dc voltage regulator and reactive power controller. In each VSC station, the main component, VSC, is a 6-IGBT bridge three-level NPC converter. The VSCs adopt the SPWM modulation technique, which compares modulation waves with two triangle carriers. The frequency of the triangle carrier wave is 1350 Hz. - Case study 1: 0 1 2 3 4 5 6 7 8 9 10 0 10 20 A m pl itu de (O hm ) (a) cable length is 1000 km 0 1 2 3 4 5 6 7 8 9 10 0 20 40 A m pl itu de (O hm ) (b) cable length is 380 km Harmonic order -100 0 100 P ha se a ng le (d eg ) -100 0 100 P ha se a ng le (d eg ) Fig. 7. Negative equivalent impedance response depends on the dc cable length. 0 1 2 3 4 5 6 7 8 9 10 0 1 2 x 104 Im pe da nc e (O hm ) DC seen equivalent impedance Harmonic order -100 0 100 P ha se a ng le (d eg ) 0 1 2 0 200 400 600 Fig. 6. DC-side seen equivalent impedance response of the receiving end VSC 0 2 4 6 8 10 12 14 16 18 20 0 1 2 3 (a)PoS background harmonic propagation Harmonic order M ag (% o f f un da m en ta l 0 2 4 6 8 10 12 14 16 18 20 0 2 4 6 8 (b)NeS background harmonic propagation Harmonic order M ag (% o f f un da m en ta l No harmonic 2nd 5th 7th Fig. 9. Different background harmonics on the sending ac system causing spectra of phase current on the receiving ac system. 2151 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 7/8 0 5 10 15 20 0 2 4 6 Harmonic order (a) lcab=1000 km , THD= 6.85% M ag (% o f F un da m en ta l) 0 5 10 15 20 0 2 4 6 Harmonic order (b) lcab=380 km , THD= 8.04% M ag (% o f F un da m en ta l) Fig. 10. Spectra of receiving end ac system phase a current when the sending ac system has un-symmetric single phase-to- ground fault. 0 2 4 6 8 10 12 14 16 18 20 0 2 4 6 8 (a) 100% power transfer capacity Harmonic order M ag (% o f f un da m en ta l 0 2 4 6 8 10 12 14 16 18 20 0 4 8 12 (b) 50% power transfer capacity Harmonic order M ag (% o f f un da m en ta l Fault 2nd 5th 7th Fig. 11. Harmonic propagation in different operation conditions of the VSC-based HVDC system. The first case was examined with 10% of a 2nd order background harmonic voltage. As the rules of harmonic transfer, the receiving end ac system induced the dc component and the 2nd order harmonic, or the 2nd order and the 4th order harmonics, which is relative to the sequence of harmonic source. The simulation results in this case are presented in Fig.8 which conformed to the analytical rules. For the same amplitude, the negative-sequence 2nd component (a) gave stronger effect than the positive-sequence 2nd component (b). It should also put attention to the appearance of the 5th and the 7th harmonics because of the dc-capacitor voltage ripples. They could be problematic if the system resonates at these frequencies. The rules were the same for the other order of harmonics, but the effect of different sequence was not so clear as can be seen in Fig.9. - Case study 2: A single phase-to-ground fault at the point of common coupling at the sending end ac system was considered in this case. As a result, the voltage was composed of the negative-sequence fundamental component propagated to the receiving end ac system and produced an additional 3rd order harmonic (see Fig. 10). - Case study 3: According to the results from the case study 1 and 2, in this case, the VSC-based HVDC system operates at different power transfer conditions. The sending end ac system includes the negative-sequence 2nd and 5th harmonics, the positive-sequence 7th harmonic. The sending end ac system in single phase-to-ground fault condition was also examined in this case. Figure 11 plots the simulation results show that decreasing in power transfer capacity gave a larger effect of harmonic propagation, especially at the negative-sequence 2nd harmonic. VI. CONCLUSION This paper uses the space vector of switching function to study the harmonic interaction between the two ac-sides of the VSC. This space vector of switching function comprises of the fundamental component, higher-order positive- and negative-sequence switching components. They support a straightforward tool to understand the origin of non-characteristic harmonics on both sides of the VSC. However, in a different way, other non-characteristic harmonics are produced on the ac-side of the VSC because of dc-capacitor ripples. Moreover, the impedance-frequency characteristic of the VSC-based HVDC system was analyzed to show at which frequencies the system resonates. The combination of the mathematical analysis of harmonic interaction and the impedance-frequency characteristic gives a thorough view of understanding harmonic propagation of VSC-based HVDC systems. After that, the simulation model of the system was set up. The simulation results agreed with the theoretical analysis in all cases. APPENDIX A. Bessel function: dee j J jkjkk cos .2 1 k k k JJ 1 B. Space vector representation of harmonics: For the three-phase harmonic quantity ˆ cos ˆ cos 2 / 3 ˆ cos 2 / 3 na nb nc f t f n t f t f n t n f t f n t n The space vector representation has the form of 2 41 1 3 3 2 41 1 3 3 ˆ 1 3 ˆ + 1 3 j n j n jn t j n j n jn t ff e e e f e e e C. Parameters of studied VSC-based HVDC system 1. Sending end: Uac1 = 345 kV, f = 50 Hz, Iscmax = 50 kA; Sb1 = 600 MVA, 345/300 kV 2. DC-link PDC = 600 MW, UDC = 300 kV, IDC = 1kA DC capacitor: Cd = 30 F; Cable: Rc = 13.9 m /km, Lc=0.159 mH/km, Cc =0.231 F/km, Lcab = 1000 km 2152 Session 4 2014 International Conference on Power System Technology (POWERCON 2014) Chengdu, 20-22 Oct. 2014 POWERCON 2014 Paper No CP1493 Page 8/8 3. Receiving end: Uac2 = 230 kV, f = 50 Hz, Iscmax = 40 kA; Sb2 = 600 MVA, 230/300 kV REFERENCES [1] Nikolas Flourentzou, Vassilios G. Agelidis, and Georgios D. Demetriades, “VSC-based HVDC Power Transmission Systems: An Overview ,” IEEE Trans. Power Electronics, vol. 24, No. 3, pp. 592–602, Mar. 2009. [2] Lihua Hu, Robert Yacamini, “Harmonic Transfer through Converters and HVDC links,” IEEE Trans. Power Electronics, vol. 7, No. 3, pp. 514–524, Jul. 1992. [3] A. E. Hammad, “Analysis of Second Harmonic Instability for the Chateauguay HVDC/VSC scheme,” IEEE Trans. Power Delivery, vol. 7, No. 1, pp. 410–415, Jan. 1992. [4] Ying Jiang, Ake Ekstrom, “General Analysis of Harmonic Transfer through Converters,” IEEE Trans. Power Electronics, vol. 12, No. 2, pp. 287–293, Mar. 1997. [5] Liangxiang Tang, Boon-Teek Ooi, “Converter Nonintegral Harmonics from AC network Resonating with DC Network,” in Pros. Industry Applications Soc. Conf. Rec. 2001, vol. 4, pp. 795–802. [6] Amirnaser Yazdani, Reza Iravani, Voltage-Sourced Converters in Power Systems. New Jersey: IEEE Press, 2010, ch. 4. [7] O. Alonso Sadaba, P. Sanchis Gurpide, and et al., “Voltage harmonics generated by 3-level converters using PWM natural sampling,” in Proc. 32nd Annu. Power Electronics Specialists Conference, Vancouver, 2001, pp. 1561-1565. [8] Stamatios K. Kartalapoulos, and et al., Pulse Width Modulation for Power Converters. Piscataway, NJ: IEEE Press, 2003, pp. 453–530. [9] Guibin Zhang, Zheng Xu , Guangzhu Wang, “Control Strategy for Unsymmetrical Operation of HVDC-VSC based on the improved instantaneous reactive power theory,” In IEEE Int. Conf. AC-DC Power Transmission, London, UK, 28-30 November 2001, pp. 262-267. [10] Guangfu Yang, VSC-based HVDC Transmission System Technology (In Chinese). Beijing, China: China Electric Power Press, 2009, pp. 172–177. [11] Chang Hsin Chien, Richard W. G. Bucknall, “Analysis of Harmonics in Subsea Power Transmission Cables Used in VSC-HVDC Transmission Systems Operation Under Steady-State Conditions,” IEEE Trans. Power Delivery, vol. 22, No. 4, pp. 2489–2497, Oct. 2007. 2153 Session 4
欢迎咨询51作业君